Service entrance diagram labelled with both IEC and NEC earthing and grounding terms

IEC vs NEC: Earthing, Grounding and Bonding Terms Compared

Put an IEC-trained engineer and an NEC-trained engineer in front of the same switchboard and they will describe the same green-yellow conductor in different words. On international projects, that mismatch causes real errors. “Ground” gets read as “neutral”, or the neutral–earth link ends up in two places.

Quick answer: IEC “earthing” is NEC “grounding”. The IEC protective conductor (PE) is the NEC equipment grounding conductor (EGC). The IEC earthing conductor is the NEC grounding electrode conductor (GEC). The IEC neutral (N) is the NEC grounded conductor. The NEC main bonding jumper corresponds to the point where the PEN is split into N and PE at the origin of a TN-C-S installation. “Bonding” means equipotential bonding in both systems. A typical NEC service is a TN-C-S arrangement in IEC terms.

The terms side by side

IEC / EN (and BS 7671)NEC (NFPA 70)What it is
EarthingGroundingConnection to the general mass of earth
Neutral conductor (N)Grounded conductor (usually the neutral)Current-carrying conductor connected to the earthed point of the source
Protective conductor (PE), circuit protective conductor (CPC, UK)Equipment grounding conductor (EGC)Conductor that connects exposed metal parts to the earthing point; carries fault current only
PEN conductorGrounded service conductor (neutral bonded at the service)Combined neutral and protective conductor ahead of the origin
Earthing conductorGrounding electrode conductor (GEC)Conductor from the main earthing terminal to the electrode
Earth electrodeGrounding electrode (rod, ring, concrete-encased “Ufer”)Conductive part in contact with the soil
Foundation earth electrodeConcrete-encased electrodeElectrode in the building foundation
Main earthing terminal (MET)Grounding/bonding point at the service equipmentThe point where earthing and bonding conductors meet
PEN split at the origin (TN-C-S)Main bonding jumperThe single neutral-to-earth link of the installation
Earthed star point of a generator or transformerSystem bonding jumper (separately derived system)The neutral-to-earth link at a new source
Protective equipotential bondingBondingConnecting metal parts so they stay at the same potential
Earth faultGround faultA fault between a live conductor and earthed metal
RCD, 30 mA additional protectionGFCI (≈ 4–6 mA) for personnelResidual-current protection of people
Earth-fault protection at the originGFPE (ground-fault protection of equipment)Protection of large services against arcing earth faults
IEC / EN term NEC term Tx PEN conductor grounded service conductor Origin / service equipment N bar PE bar PEN split (TN-C-S) main bonding jumper main earthing terminal grounding / bonding point one N–PE link only Load protective conductor PE equipment grounding conductor (EGC) earthing conductor grounding electrode conductor (GEC) earth electrode grounding electrode pipe main protective bonding bonding (bonding jumper)
The same service entrance with both vocabularies. IEC calls this TN-C-S; in an NEC service the neutral is bonded to the grounding system only at the service.

Practical differences beyond the words

TopicIEC 60364 practiceNEC practice
Earthing systemsTN-S, TN-C-S, TT, IT named and chosen per projectSolidly grounded systems, in effect TN-C-S with the neutral bonded at the service only; ungrounded and impedance-grounded systems used in industry
PE / EGC sizingFrom the phase size (S ≤ 16 → S; ≤ 35 → 16; above → S/2) or an adiabatic checkFrom the rating of the overcurrent device, using the NEC table
Electrode resistanceTarget set by system: TT RA × IΔn ≤ 50 V, LPS ≤ 10 Ω where possibleSingle rod ≤ 25 Ω, otherwise a supplemental electrode
Shock protectionAutomatic disconnection with time limits; 30 mA RCD as additional protectionEGC and overcurrent device clear faults; GFCI in specified locations; AFCI in dwellings
ColoursPE green-yellow, N blueEGC green, green-yellow or bare; grounded conductor white or grey

Typical values — verify with the edition adopted locally.

What this means on a project

  • Neither system is “right”. The one adopted by the authority where the building stands applies. Many Middle East and Asian projects mix IEC equipment with US-trained staff, so put a terms table on the general notes sheet.
  • Never write just “ground”. Write “PE (EGC)” or “N (grounded conductor)” on drawings that serve both audiences.
  • One neutral-to-earth link per source. This is identical in both systems. A second link downstream makes neutral current flow on PE and metalwork, and RCDs or GFPE trip at random.
  • Generators and transformers create a new source. The NEC calls this a separately derived system with its own system bonding jumper. In IEC terms the star point is earthed at the set, and a 4-pole changeover is then needed.
  • Sizes do not convert exactly. 12 AWG ≈ 3.3 mm², 10 AWG ≈ 5.3 mm². Size a conductor under the code that applies; do not convert it from the other code.
Copper busbars in a distribution board with green-yellow protective conductors and blue neutral conductors connected
Copper bars in a board, with green-yellow protective and blue neutral conductors. The protective (PE) bar is the main earthing terminal in IEC language, the grounding and bonding point of the service in NEC language. Photo: Asurnipal, CC BY-SA 4.0, via Wikimedia Commons

Related reading: TN, TT and IT earthing systems explained, how to measure earth electrode resistance and RCD types AC, A, F and B.

Online course · certificate included

Electrical Power Systems Design for Buildings

35 modules from the MV connection to the socket: transformers, short circuit, protection and selectivity, cable sizing, boards, generators, earthing, surge and lightning protection. Includes 50 % off TEKHAT.

Modules 1–3 are free, no account needed · full course €15,00 one-time

Start freeView the course

FAQ

Is earthing the same as grounding?

Yes. Earthing is the IEC and British term and grounding is the North American term for connecting a system or equipment to the general mass of earth. The design rules behind the words differ, but the physical concept is the same.

What is the IEC equivalent of an equipment grounding conductor?

The protective conductor (PE), called the circuit protective conductor (CPC) in the UK. It connects exposed metal parts to the earthing point and carries current only during a fault.

What is a main bonding jumper in IEC terms?

It is the connection between the neutral and the protective earthing system at the service. In IEC terms this is where the PEN conductor is split into N and PE at the origin of a TN-C-S installation, and it must exist only once.

Is the NEC grounded conductor the same as the ground wire?

No. The grounded conductor is normally the neutral, which carries load current. The “ground wire” is the equipment grounding conductor, which carries current only during a fault. Mixing them up is a common and dangerous error.

MEP Center software

TEKHAT – Single-Line Diagram & Load Schedule

Draw panel single-line diagrams and load schedules in minutes, with breaker, RCD and cable sizing. Buyers of the Electrical Power Systems Design course get 50 % off.

Free install from the Microsoft Store · 30-day trial · licence 20 € for all your devices or €15 per computer on our site

Get it from MicrosoftSee the program

Leave a Comment

Your email address will not be published. Required fields are marked *

Shopping Cart