Supply side of a 2.0 m³/s air handling unit with the pressure drop of each section

AHU Sizing: Quick Rules for Airflow, Coil and Footprint

The architect wants to know how big the plant room must be, and the AHU selection software is not open yet. You need an airflow, a casing cross-section, a coil duty and a footprint you can defend in ten minutes, and that later matches the manufacturer’s selection.

Quick answer: Size the airflow from the sensible load, q (L/s) = Qs (W) / (1.2 × ΔT), or from the outdoor air rate for a 100 % outdoor air unit. Divide the airflow by about 2.0 m/s to get the casing cross-section, keep the cooling coil face velocity at 2.0–2.5 m/s, and add the coil and fan duties from the air side. Then add access clearances: coil withdrawal on one side (unit width + about 300 mm), 0.6 m at the back and a 150–200 mm plinth for the condensate trap.

Step 1: airflow

For a recirculating unit serving a cooled space, the supply airflow comes from the room sensible load and the supply temperature difference:

q = Qs / (1.2 × ΔT)

where q is in L/s, Qs is the room sensible load in W and ΔT is the room-minus-supply temperature in K. 1.2 kJ/(m³·K) is ρ·cp of air. At ΔT = 10 K this gives about 83 L/s (300 m³/h) per kW of sensible load. Take the load from a proper block calculation, not from the sum of room peaks (see cooling load calculation basics).

For a dedicated outdoor air system (DOAS), the airflow is the ventilation rate itself: people plus area, not an ACH figure from the brief. The rates and how the two main standards differ are in ASHRAE 62.1 vs EN 16798.

Step 2: casing and coil size

Acasing = q / vcasing, with vcasing ≈ 2.0 m/s for a normal comfort unit (around class V3 in EN 13053, which runs from V1 ≤ 1.6 m/s to V9 > 3.6 m/s). A lower velocity means a bigger, more expensive unit with lower pressure drops and fan energy; a higher velocity saves space and costs energy for 20 years.

The finned area of the cooling coil is a little smaller than the casing cross-section, so check its face velocity separately: 2.0–2.5 m/s for cooling coils. Above about 2.5–2.8 m/s condensate is torn off the fins and carried into the fan unless a droplet eliminator is fitted. Heating coils can run at 2.5–3.0 m/s.

Step 3: coil and fan duties

  • Cooling coil: Q = ṁ × (hon − hoff) in kW, with ṁ in kg/s and h in kJ/kg from the psychrometric chart (AHU processes on the chart). Chilled water flow = Q / (4.19 × ΔTw) in kg/s.
  • Heating coil: Q = 1.2 × q(m³/s) × ΔT in kW, after heat recovery.
  • Fan: Pel = q × Δptotal / (ηfan × ηmotor), with q in m³/s and Δp in Pa giving W. Check the fan at the dirty filter pressure, not only the average.

Worked example: office DOAS, 2.0 m³/s (7200 m³/h), 100 % outdoor air, counterflow plate heat exchanger 75 %, summer outdoor 34 °C / 14.0 g/kg, extract 25 °C, coil-off 13 °C / 8.62 g/kg, chilled water 6/12 °C.

  1. Casing: 2.0 / 2.0 = 1.0 m² → internal 1.25 m wide × 0.80 m high.
  2. Cooling coil finned area ≈ 0.80 m² → face velocity 2.0 / 0.80 = 2.5 m/s (at the upper limit; a slightly larger casing would bring it to 2.2 m/s).
  3. After heat recovery: 34 − 0.75 × (34 − 25) = 27.25 °C, h 63.1 kJ/kg; coil-off h 34.8 kJ/kg. Mass flow ≈ 2.40 kg/s.
  4. Cooling coil: 2.40 × (63.1 − 34.8) = 67.9 kW (84.7 kW without heat recovery). Water: 67.9 / (4.19 × 6) = 2.70 kg/s. Condensate: 2.40 × (14.0 − 8.62) = 12.9 g/s = 46.5 kg/h.
  5. Pressure: internal 700 Pa + external 450 Pa = 1150 Pa fan total.
  6. Fan: 2.0 × 1150 / (0.70 × 0.90) = 3.65 kW electrical → SFP 3.65 / 2.0 = 1.83 kW/(m³/s), class SFP4.

Sanity check: 67.9 kW / 2.0 m³/s ≈ 34 kW per m³/s of outdoor air, a normal figure for a hot, humid design day with heat recovery.

Supply side of a 2.0 m³/s DOAS unit: pressure drop per section Outdoordamper PrefilterePM10 PlateHX 75 % Heatingcoil Coolingcoil Supplyfan Final filterePM1 Silencer 15 Pa110 Pa160 Pa40 Pa150 Pa175 Pa50 Pa +1150 Pa drain pan + trap OASA Internal 700 Pa + external 450 Pa = fan total 1150 Pa (dirty filters: 1275 Pa) Casing 1.25 × 0.80 m = 1.0 m² → 2.0 m/s · cooling coil 0.80 m² → 2.5 m/s face Fan 2.0 m³/s × 1150 Pa / (0.70 × 0.90) = 3.65 kW → SFP 1.83 kW/(m³/s)
Section-by-section pressure build-up of the worked DOAS unit. The coils, heat exchanger and filters set most of the fan power, so a slightly larger casing pays back.

Rule-of-thumb table

ItemTypical valueNote
Supply airflow per kW sensible83 L/s (300 m³/h) at ΔT 10 Kq = Qs / (1.2 ΔT)
Casing velocity≈ 2.0 m/sLower = bigger unit, less fan energy
Cooling coil face velocity2.0–2.5 m/sAbove ≈ 2.5–2.8 m/s: carry-over
Heating coil face velocity2.5–3.0 m/s1–2 rows, 20–60 Pa
Cooling coil rows / air ΔP4–8 rows; 6 rows wet 120–200 PaMore rows, lower bypass factor
Coil water-side ΔP≤ 30–50 kPaCounterflow connection
Heat recovery efficiencyWheel 70–85 %, counterflow plate 75–90 %, run-around 40–60 %Ecodesign minimum 73 % (run-around 68 %)
SFP class (EN 16798-3)SFP3 ≤ 1250, SFP4 ≤ 2000 W/(m³/s)Check against local energy rules

Step 4: footprint and plant room

Unit length depends on the sections you include (heat recovery, humidifier, silencers), so take it from a quick selection or a similar past project. Width and clearances you can fix now:

  • Coil withdrawal side: unit width + about 300 mm, so a coil comes out in one piece; 1.0–1.2 m in front of every access door and filter section.
  • Back side: 0.6 m minimum, more where valves, pipes and traps sit.
  • Plinth: 150–200 mm or more, so the condensate trap fits under the drain connection (see condensate trap design).
  • Delivery route: units arrive in sections; check doors, lifts and weights before the plant room is frozen.

For the example, with a casing about 1.35 m wide outside, the plant room needs roughly 0.6 + 1.35 + 1.65 = 3.6 m of width, before ducts and pipes.

Free tool: MEP unit converter — switch between m³/s, m³/h, L/s and cfm, or kW and TR, while you size the unit.

Typical values — verify with the edition adopted locally.

Online course · certificate included

HVAC Systems Design — Heating, Cooling & Ventilation

28 modules from heat loss to plant room: boilers, heat pumps, cooling loads, psychrometrics, AHUs and ductwork. The VRF course is included.

Modules 1–3 are free, no account needed · full course €15,00 one-time

Start freeView the course

FAQ

What face velocity should an AHU cooling coil have?

2.0–2.5 m/s across the finned area. Above about 2.5–2.8 m/s condensate droplets are carried off the fins into the fan and ductwork unless a droplet eliminator is fitted.

How do I estimate AHU airflow from the cooling load?

Use q (L/s) = sensible load (W) / (1.2 × ΔT). At a 10 K supply temperature difference that is about 83 L/s, or 300 m³/h, per kW of sensible load.

How much space does an AHU need around it?

On the coil side, the unit width plus about 300 mm for coil withdrawal and 1.0–1.2 m in front of access doors; 0.6 m at the back; and a 150–200 mm plinth for the condensate trap. Confirm with the manufacturer.