Stair Pressurisation: Quick Airflow Design

A pressurised stair has to meet three conditions at once: enough pressure to keep smoke out with the doors closed, enough air velocity through an open door, and a door that people can still open. The fan size falls out of the first two; the third catches designs that over-pressurise. Here is a quick estimate you can do before the specialist calculation.

Quick answer: Calculate the leakage through the closed doors with Q = 0.83 × A × √Δp at the design pressure (often 50 Pa in European practice), add 25–50 % for unidentified leakage, then calculate the open-door case as door area × required velocity (0.75 m/s or 2 m/s) plus leakage at the reduced pressure. Size the fan for the larger case. Then check the door opening force (limit 100 N in European practice, 133 N in US codes) and provide pressure relief and a release path from the fire floor.

The formulas

Leakage through a closed door: Q = 0.83 × A × Δp0.5 (Q in m³/s, A = leakage area in m², Δp in Pa).

Open door: Q = Adoor × v (v = required air velocity through the doorway, m/s).

Door opening force: F = Fdc + (W × A × Δp) / (2 × (W − d)), with Fdc = door closer force (N), W = door width (m), A = door area (m²), d = distance from the handle to the door edge (m).

Criteria side by side

CriterionEuropean approach (EN 12101 series)US approach (NFPA 92)
Pressure, doors closedTraditionally ≈ 50 Pa for many system classesMinimum ≈ 12.5 Pa in sprinklered buildings; higher without sprinklers
Velocity, doors open≈ 0.75 m/s (some evacuation classes); 2 m/s (firefighting classes)No fixed door velocity; minimum pressure differences maintained with the design number of doors open
Door opening force100 N133 N (30 lbf), per life-safety code

EN 12101-6 is being superseded by EN 12101-13; check which edition and system class your fire strategy uses. Which approach applies is set by the local code and the fire engineer, not by preference.

Worked example: 12-door stair

Inputs: 12 doors including roof and final exit, leakage area 0.02 m² each; design pressure 50 Pa; open-door criterion 0.75 m/s through one 0.9 × 2.0 m door (1.8 m²).
Closed doors: 0.83 × 0.02 × √50 = 0.83 × 0.02 × 7.07 = 0.117 m³/s per door → × 12 = 1.41 m³/s; + 25–50 % unidentified leakage → 1.8–2.1 m³/s.
Open door: 1.8 × 0.75 = 1.35 m³/s, plus the 11 closed doors at the remaining ≈ 10 Pa: 11 × 0.83 × 0.02 × 3.16 = 0.58 m³/s → ≈ 1.9 m³/s.
Fan: both cases are similar here → about 2.1 m³/s before duct leakage and margins. With a 2 m/s criterion the open door alone would need 3.6 m³/s and would govern by far.
Door force (0.9 × 2.1 m door, A 1.89 m², closer 40 N, handle 60 mm from the edge): 40 + (0.9 × 1.89 × 50) / (2 × 0.84) = 40 + 50.6 = 90.6 N ✓ (≤ 100 N, little margin).
Sanity check: if all doors close and the pressure rises to 80 Pa, F = 40 + 81 = 121 N ✗ — this is why pressure relief is essential.
Pressurised stair — the three checks supply fan relief damper +50 Pa doors closed fire floor smoke door open 0.75 m/s release vent on the fire floor final exit (open in evacuation) 1 Closed doors 12 × 0.117 = 1.41 m³/s 2 Open door 1.35 + 0.58 ≈ 1.9 m³/s 3 Door force 90.6 N at 50 Pa ≤ 100 N No release path → velocity fails, smoke enters
Supply at the top, relief damper against over-pressure, and a release vent on the fire floor so that the air through the open door has somewhere to go.

Design checks that are often missed

  • Release path: without vents, a shaft or mechanical extract on the fire floor, the air through the open door has nowhere to go and the velocity criterion fails.
  • Pressure relief: a barometric relief damper or a variable-speed fan controlled on stair pressure keeps the door force below the limit when doors close.
  • Intake position: outdoor air from a point that smoke cannot reach — never next to smoke exhaust or car-park outlets.
  • Tall buildings: stack effect changes the pressure difference with height; use several injection points.
  • Power and controls: fire-rated supplies and cables, and a cause-and-effect matrix with the fire alarm.
  • Commissioning: measure pressure, door velocity and door force on site; see the HVAC commissioning checklist.

Related reading: fire alarm cause and effect matrix, car park ventilation with jet fans and the duct sizing guide for the supply shaft.

Free tool: MEP unit converter — convert the fan duty between m³/s, m³/h and cfm, and Pa to in. w.g.

Typical values — verify with the edition adopted locally. This is a quick estimate; the pressurisation system is a life-safety system and its final design follows the fire strategy and the specialist calculation.

Online course · certificate included

HVAC Systems Design — Heating, Cooling & Ventilation

28 modules from heat loss to plant room: boilers, heat pumps, cooling loads, psychrometrics, AHUs and ductwork. The VRF course is included.

Modules 1–3 are free, no account needed · full course €15,00 one-time

Start freeView the course

FAQ

What pressure is used for stair pressurisation?

European practice has traditionally used about 50 Pa with the doors closed for many system classes. NFPA 92 sets a minimum of about 12.5 Pa in sprinklered buildings and higher values without sprinklers.

How do I estimate the airflow for a pressurised stair?

Calculate leakage through all closed doors with Q = 0.83 × A × √Δp and add 25–50 % for unidentified leakage. Then calculate the open-door case as door area times required velocity plus leakage at the reduced pressure, and use the larger result.

What is the maximum door opening force?

About 100 N in European practice and 133 N (30 lbf) in US life-safety codes. Pressure relief or fan speed control is needed so that the force stays below the limit when all doors are closed.