Sample fire alarm cause and effect matrix with input rows, output columns and actions in each cell

How to Write a Fire Alarm Cause and Effect Matrix

A fire alarm system does not evacuate a building on its own: it stops fans, closes dampers, recalls lifts, releases doors and starts pressurisation fans. The cause and effect matrix is the one document that says exactly which input does what, and it is the document most often argued about at commissioning. Here is how to write one that the mechanical, electrical and architectural teams can all sign.

Quick answer: A cause and effect matrix is a table with one row per input event (a detection zone, detector group, call point group, sprinkler flow switch, suppression signal) and one column per output (sounders by alarm zone, lifts, dampers, AHUs, pressurisation, door holders, access control, gas valves). Each cell states the action and any delay or condition. NFPA 72 calls it the input/output matrix. Build it from the fire strategy, agree it with every discipline, then test every cell at commissioning.

Step by step

  1. Start from the fire strategy, not from the panel. Read the evacuation strategy (simultaneous or phased), the smoke control concept, compartments and lift strategy. Why: every output in the matrix must trace back to a decision in the strategy.
  2. List the inputs (causes) as rows. Group them as the strategy needs: “any automatic detector, floor 3”, “call points, floor 3”, “car park detectors”, “kitchen heat detectors”, “sprinkler flow switch zone 2”, “suppression discharged, server room”, plus supervisory inputs such as valve tamper and fire pump running. Why: rows grouped by zone keep the matrix readable; individual devices only where they act differently.
  3. List the outputs (effects) as columns. Sounders or voice messages per alarm zone, lift recall, stair pressurisation, smoke dampers, smoke exhaust fans, AHU shutdown, door holder release, access control release, gas shut-off valves, signals to the BMS and the remote monitoring centre. Why: each column becomes one output module or one interface you must wire.
  4. Fill each cell with an action, not a tick. Write “close”, “stop”, “start”, “recall to ground”, “alert tone”, “evacuate message” — plus any delay. Why: “✓” in the dampers column does not say whether the damper opens (extract) or closes (isolation).
  5. Define the logic. Single-knock (one device triggers) for most outputs; coincidence or double-knock (two devices) for gas suppression release and other drastic actions; investigation delays only where the authority accepts them. Why: logic is where false alarms and missed actions are born.
  6. Add the lift rules. Lifts return to the main recall floor; if the fire is detected in the main floor lobby itself, they go to the alternate floor. Why: a lift must never deliver people into the fire floor lobby.
  7. Separate fire commands from monitoring. Fire actions go through fire alarm output modules; the BMS only receives status via Modbus/BACnet. Why: a BMS fault must never stop a fire action.
  8. Review and sign. Mechanical (dampers, fans, pressurisation), electrical (lifts, power), architectural (doors, access control) and the fire strategist sign the same revision. Why: one signed revision ends the commissioning arguments.
  9. Test every non-empty cell. At commissioning, trigger each row and record each output’s response and time. Why: the signed, tested matrix is your proof of performance.
Inputs (causes) as rows, outputs (effects) as columns Soundersalarm zone Liftsrecall Stairpressuris. Smokedampers AHUfloor Doors /access Any detector, floor 3 Call point, floor 3 Detector, ground lobby Kitchen heat detector Server room, 2 detectors Evac: F3, F4Alert: others To ground Start F3 extractopen Stop F3 Release Evac: F3, F4To groundStart——Release Evac: GFTo alternateStartGF openStop GFRelease Evac: kitchen——Hood dampercloseStop— Room only+ countdown——CloseStopRelease Each cell is an action. Red: lobby detector on the main recall floor sends lifts to the alternate floor. Server room row is coincidence (double-knock): two detectors before gas release countdown.
A compact matrix for a small office building with phased alarm (fire floor and floor above evacuate, others get an alert tone).

What a good cell looks like

Weak entryBetter entry
✓ DampersSmoke extract dampers floor 3: open. Isolation dampers floor 3: close.
✓ SoundersEvacuate message floors 3 and 4; alert tone all other floors.
✓ LiftsRecall to ground; if ground lobby detector, recall to alternate floor (level 1).
✓ Gas suppressionTwo detectors in room (coincidence): pre-alarm, close dampers, 30 s countdown, release.
Example row count. A five-storey office with one detection zone per floor, separate call point groups per floor, a car park, a kitchen and one server room: 5 detector rows + 5 call point rows + car park + kitchen + server room + 3 supervisory rows (sprinkler flow, valve tamper, fire pump running) = 16 rows. With 10 output columns, that is at most 160 cells to test — plan a full day for it at commissioning.

Common mistakes

  • Ticks instead of actions, so nobody knows whether a damper opens or closes.
  • Smoke control fans stopped by a general “all HVAC off” command.
  • No alternate floor rule for the lift lobby on the recall floor.
  • Gas release on a single detector, causing an expensive discharge on a false alarm.
  • Fire commands routed through the BMS instead of fire alarm output modules.
  • Matrix not updated after a strategy change, so the panel programming and the drawings disagree.

The matrix depends on the zones and alarm zones you set; see fire alarm system types and fire alarm loop design for the output modules each column needs. For server room actions, read clean agent fire suppression for server rooms.

Online course · certificate included

Fire Detection and Alarm System Design

Detector selection and layout, loops, panels, voice alarm and real DXF projects to EN 54-14 and NFPA 72.

Modules 1–3 are free, no account needed · full course €8,00 one-time

Start freeView the course

FAQ

What is a cause and effect matrix in a fire alarm system?

It is a table that lists every input event as a row and every output as a column, with the required action and any delay in each cell. It defines how the fire alarm panel controls lifts, dampers, fans, doors, sounders and other systems.

Who prepares and signs the cause and effect matrix?

The fire alarm designer usually drafts it from the fire strategy. Mechanical, electrical, architectural and fire strategy teams review it and sign the same revision, and it is tested line by line at commissioning.

What is the NFPA 72 equivalent of a cause and effect matrix?

NFPA 72 calls it the input/output matrix of operation. It is part of the design documents and is used to verify every function during acceptance testing.

Leave a Comment

Your email address will not be published. Required fields are marked *

Shopping Cart