Section through a heated floor with tiles, screed, pipes at 150 mm, insulation and slab, showing upward and downward heat flux

Underfloor Heating: Quick Design Rules

Underfloor heating looks simple on a drawing — a manifold and some loops — but a few numbers decide whether it works: the heat flux per square metre, the surface temperature limit, and the one room that drags the flow temperature of the whole house up. Here is the quick design sequence with a worked room.

Quick answer: Divide each room’s heat loss by the floor area that actually has pipes. Keep it below about 100 W/m² for occupied areas (29 °C surface) — more needs an edge zone or a second emitter. Read the required water-to-room temperature difference from the system’s characteristic curve, add the room temperature and half the water spread to get the flow temperature, and let the worst room set it. Then check circuit length (about 100–120 m for 16 mm pipe) and pressure drop (below 20–25 kPa).

The formulas

Heat flux: q = ΦHL / AF (W/m²), with AF excluding fixed furniture, kitchen units and shower trays.

Surface temperature: q = 8.92 × (θF,m − θi)1.1 → Δθ = (q / 8.92)1/1.1. θF,m = mean floor surface temperature, θi = room temperature.

Flow temperature: q = KH × ΔθH → θV = θi + ΔθH + σ/2. KH (W/m²K) comes from the manufacturer’s tested curve for the spacing and floor covering; ΔθH is the log-mean water-to-room difference; σ is the water spread, at most 5 K in the design room.

Pipe length: about 1/spacing metres per m²: 100 mm → 10 m/m², 150 mm → 6.7 m/m², 200 mm → 5 m/m².

Worked example: 18 m² living room

Inputs: heat loss 904 W, AF 18 m², room 20 °C, tiles (Rλ,B 0.10 m²K/W), 16 mm pipe at 150 mm, illustrative KH = 3.4 W/m²K, σ = 5 K.
Flux: 904 / 18 = 50.2 W/m² — well below 100 ✓.
Surface: (50.2 / 8.92)0.909 = 4.81 K → 24.8 °C ✓ (limit 29 °C).
Flow temperature: ΔθH = 50.2 / 3.4 = 14.8 K → θV = 20 + 14.8 + 2.5 = 37.3 °C.
Water flow (ground-floor slab, downward losses included, factor 1.195): 18 × 50.2 / (5 × 4 190) × 1.195 = 0.0515 kg/s = 186 kg/h.
Pipe: 18 × 6.7 = 120 m + leads 2 × 8 m = 136 m → too long for one 16 mm loop → two circuits of ≈ 76 m (≈ 60 m in the room + 16 m leads each), 93 kg/h each, ≈ 0.23 m/s, ≈ 87 Pa/m → ≈ 7.9 kPa with fittings ✓.
Sanity check: downward loss ≈ 9.8 W/m² (≈ 176 W, 19 % of the room load) — that is why insulation under the pipes matters.
Heated floor section — worked living room Room 20 °C q = 50.2 W/m² up surface 24.8 °C (limit 29 °C) 150 mm tiles + adhesive (R 0.10) cement screed ≥ 45 mm over pipe 16 mm pipe: flow red, return blue insulation (R ≈ 2.0) slab on ground (≈ 10 °C) q down ≈ 9.8 W/m² (19 % of load) Flow 37.3 °C · two circuits of ≈ 76 m · 93 kg/h each · ≈ 7.9 kPa
Pipe spacing is measured between adjacent pipes (150 mm here). In a bifilar spiral flow and return pipes alternate, which keeps the surface temperature even. The numbers are those of the worked room.

The worst room sets the flow temperature

All circuits on one manifold get the same water. In the same house the 5 m² bathroom (24 °C, 430 W) needs 86 W/m²: surface 31.9 °C (limit 33 °C ✓), but with 100 mm spacing and KH ≈ 5.44 the flow must be 24 + 15.8 + 2.5 = 42.3 °C — 5 K above the living room. A 150 W towel radiator drops the floor’s share to 56 W/m² and the bathroom’s need to 36.8 °C. The living room then governs and the design flow becomes ≈ 38 °C. On a heat pump that is worth roughly 10–15 % in efficiency.

Rules of thumb

ItemTypical value
Surface limit, occupied zone29 °C → ≈ 100 W/m² (room 20 °C)
Bathroom limitθi + 9 K = 33 °C → ≈ 100 W/m²
Edge zone (≤ 1 m strip at glazing)35 °C → ≈ 175 W/m²
Spacing 300 → 150 mm≈ +25–45 % output
Carpet instead of tiles≈ −30–50 % output
Circuit length≈ 100–120 m (16 mm), 120–150 m (20 mm)
Circuit pressure dropbelow ≈ 20–25 kPa, balanced at the manifold
Manifold sizeup to ≈ 10–12 circuits
Screed covercement ≥ 45 mm, calcium sulphate ≥ 35 mm
Screed bays≤ 40 m², ≤ 8 m side, ≤ 2:1
Safety limiter on a mixing station≈ 50–55 °C
Free tool: Heating pipe size calculator — size the manifold feed from the total kW and the 5 K spread.

Room loads come from heat loss calculation step by step. For the heat source see heat pump sizing and the bivalent point; for mixed systems with radiators, radiator sizing correction factors.

Typical values — verify with the edition adopted locally and with the manufacturer’s tested characteristic curves (the KH value above is illustrative).

Online course · certificate included

HVAC Systems Design — Heating, Cooling & Ventilation

28 modules from heat loss to plant room: boilers, heat pumps, cooling loads, psychrometrics, AHUs and ductwork. The VRF course is included.

Modules 1–3 are free, no account needed · full course €15,00 one-time

Start freeView the course

FAQ

How many watts per square metre can underfloor heating deliver?

About 100 W/m² in occupied areas, where the floor surface may reach 29 °C at a 20 °C room. Edge zones along glazing may reach 35 °C and about 175 W/m².

What flow temperature does underfloor heating need?

Room temperature plus the required water-to-room difference from the system curve plus half the water spread. A well-insulated living room at 50 W/m² needs about 37–38 °C; the worst room on the manifold sets the value for all.

How long can an underfloor heating loop be?

About 100–120 m for 16 mm pipe and 120–150 m for 20 mm, including the leads to the manifold. Longer loops exceed the pressure drop and temperature drop limits, so split the room into several circuits.